2p DC 500V/600V Sup4-S40 SPD 20/40ka DC Surge Protector Device for Solar System Protection
Current in(Ka): 20A Imax(Ka):40A
Poles Number: 2p(DC+,DC-,Gnd)
Contact Position Indication: on/off/Trip
Trademark: BLUESUNSOLAR
Transport Package: a Small Carton
Origin: China
HS Code: 8535291000
 2P 600V 40KA House Surge Protector Protective Low-voltage Arrester Device
This surge protector mainly used light volt power distribution system of lightning surge protection or other transient overvoltage. Products built for high voltage dc power supply overheating over-current protection function, can provide grade C for photovoltaic (pv) power system transient protection. Products using 35 mm DIN rail installation, module can change independently, easy to install and maintain, with remote communication alarm interface (dry contact), surge protector to facilitate remote monitoring.
Â
Technical parameters
Nominal PV System Voltage | 500V | 1000V | 1200V | |
MCOVÂ [UCPV] | 630Vdc | 1170Vdc | 1200Vdc | |
Max System Discharge Current (8/20 µs) [lmax] | 40kA | 40kA | 30kA | |
Voltage Protection Level [UP] | ≤2.5kV | ≤4.0kV | ≤4.5kV | |
Voltage Protection Level at 5kA [UP] | ≤2.0kV | ≤3.5kV | ≤4.0kV | |
Integrated Fuse Breaking Capacity/Interrupting Rating | 30kV/1000Vdc | 30kV/1000Vdc | 30kV/1200Vdc | |
Technology | Short-Circuit Interruption (SCI) Overcurrent Protection | |||
Operating Temperature Range [TU] | −40ºC to +80ºC | |||
Nominal Discharge Current (8/20 µs) [(DC+/DC−)ÂÂ> PE] [In] | 12.5kA | |||
Response Time [tA] | <25ns | |||
Operating State/Fault Indication | Green (good)/Red(replace) | |||
Conductor Ratings and CrossÂSectional Area: | Minimum | 60/70ºC 1.5mm²/14AWG Solid/Flexible | ||
Maximum | 60/70ºC 35mm²/2AWG Stranded/25mm²/4AWG Flexible | |||
Mounting | 35mm DIN Rail per EN 60715 | |||
Enclosure Material | UL 94V0 Thermoplastic | |||
Degree of Protection | IP20 | |||
Capacity | 3 Modules, DIN 43880 | |||
Standards Information: | IEC 61643Â11 Type 2,IEC 61643Â1 Class II | |||
Product Warranty | Five Years** |
Â
Remote Contact Signaling
Remote Contact Signaling Type | Changeover Contact |
AC Switching Capacity (Volts/Amps) | 250V/0.1A |
DC Switching Capacity (Volts/Amps) | 250V/0.1A; 125V0.2A; 75V/0.5A |
Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals | 60/75ºC Msx. 1.5mm²/14AWG Solid/Flexible |
Ordering Information | Order from Catalog Numbers Above |
Dimensions and Main Drawings